Innotech iSEA Uživatelský manuál Strana 30

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 44
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 29
Innotech Service & Event Analyser Installation Instructions
Page 30
© Mass Electronics Pty Ltd 2011
Edition 3.1 dated 26.03.2014
Figure 3-17: FM Builder - Add Point to an Alarm Group
13. Drag the point to the required Alarm Group, and set the ‘Activation Settings’ to ‘Changes to
0 ’.
14. Create 6 points on the ‘Chronicle Server’ device with the following addresses:
DbConnected~Output (Digital).
iCommConnected~Output (Digital).
AllocatedDB~Output (Analogue).
ReportingUsage~Output (Analogue).
DongleConnected~Output (Only relevant when a Chronicle dongle for using 10GB SQL
database has been purchased - Digital).
DatabaseLogging~Output (Only relevant when a Chronicle dongle for using 10GB SQL
database has been purchased - (Digital).
A point for SQL_ExpressRunning~Output can also be created if desired.
Zobrazit stránku 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 43 44

Komentáře k této Příručce

Žádné komentáře